Sizing a Home Battery Correctly

Why a battery must pass three tests (energy, continuous power and surge), how a critical-load list sets each one, and when partial-home backup beats buying more kWh.

Battery Economics has no affiliation with, sponsorship from, or endorsement by any manufacturer, installer, utility, aggregator, or program administrator named here.

Short answer

  • A battery has to pass three tests, not one: enough kWh for the outage, enough continuous kW for everything running at once, and enough surge for the largest motor to start.
  • Essentials are small; air conditioning is not. In our example, a refrigerator, lights, Wi-Fi, a sump pump and a gas furnace blower use about 5.1 kWh a day and peak near 3.3 kW. Adding a 3-ton central air conditioner raises that to about 18 kWh a day and a peak near 12 kW.
  • One 13.5 kWh battery covers the essentials list for about 2.3 days without solar, but less than one day once central AC is included.
  • Partial-home backup is usually the economic answer. A dedicated backup panel limits the load to what matters, so one battery can do the job of two or three.
5.1 kWhDaily energy, essentials with gas heat
18 kWhDaily energy, essentials plus 3-ton central AC
185 AMotor-start rating (LRA), Powerwall 3 and aPower 2
29.6 kWhAverage U.S. home’s daily electricity purchases

Three numbers that size a battery

Energy (kWh) is how long the battery lasts: the sum of each load’s watts times the hours it actually runs. Continuous power (kW) is how much can run at once, limited by the inverter. Surge is the brief spike when a compressor or pump motor starts, often 2 to 3 times its running draw. Batteries list it as peak kW for a few seconds or as locked-rotor amps (LRA). Powerwall 3 and FranklinWH’s aPower 2 are both rated for 185 A LRA (Tesla Powerwall 3 datasheet; FranklinWH aPower 2 datasheet).

The average U.S. home bought 10,791 kWh of electricity in 2022, about 29.6 kWh a day (EIA household electricity use). Whole-home figures like that overstate what most backup systems need to carry, because an outage is when electric dryers, ranges and EV chargers can wait.

Build the load list first

Daily energy by load: three backup scenarios

kWh per day; running watts × duty cycle × hours in use

Swipe to see the full chart →

RefrigeratorLED lightingInternet / Wi-FiSump pumpGas furnace blowerCentral AC, 3-tonWell pumpElectric water heaterElectric range0102030Essentials, gas heat5.1 kWh/dayEssentials + central AC17.6 kWh/dayMost of the home22.3 kWh/day
Battery Economics calculation using the defaults in our Battery Size Calculator: refrigerator, lighting and Wi-Fi from EnergySage backup-load guide and EnergySage household watts; sump pump from the Generac generator sizing worksheet; furnace blower from Furnace blower electrical load; central AC at 1,200 W per ton running and 3,500 W per ton starting from HVAC generator sizing reference. Real appliances vary; check the nameplate.

The same list gives the power test. Adding up running watts gives about 2.0 kW continuous for the essentials list and 5.0 kW once the air conditioner is included. Then add the largest single start-up spike on top: about 3.3 kW and 11.9 kW peak. With an electric water heater, range and well pump added, the “most of the home” case reaches about 14.0 kW continuous and 22 kWh a day.

Battery power limits vs. scenario peaks

Continuous and short-term peak kW per unit, from manufacturer datasheets

Swipe to see the full chart →

Continuous kWShort-term peak kW0 kW5 kW10 kW15 kW20 kWEnphase IQ Battery 5P3.84 / 7.68sonnenCore+4.8 / 7.2Tesla Powerwall 25 / 7LG enblock S146 / 9FranklinWH aPower 210 / 15Tesla Powerwall 311.5 / 15.4Essentials, gas heat peak 3.3 kWEssentials + central AC peak 11.9 kW
Sources: Enphase IQ Battery 5P datasheet; sonnenCore+ technical specifications; Tesla Powerwall 2 datasheet; LG enblock S datasheet; FranklinWH aPower 2 datasheet; Tesla Powerwall 3 datasheet (peak shown is the 15.4 kW off-grid rating). Peak durations differ by brand, from 3 to 10 seconds. Multiple units add power as well as energy.

From load list to battery size

Multiply daily kWh by the backup days needed, then add a margin. Our Battery Size Calculator uses a 12.5% sizing reserve, the midpoint of a 10–15% range, to cover temperature, aging and estimation error. Applied here:

  • Essentials with gas heat: 5.1 kWh × 1.125 = 5.8 kWh per day. One 13.5 kWh battery covers about 2.3 days; power needs fit within almost any single unit.
  • Essentials plus central AC: 17.6 kWh × 1.125 = 19.8 kWh per day, so two 13.5 kWh units for one full day. The 12 kW peak also rules out the smaller inverters unless a soft starter is fitted to the compressor.
  • Most of the home: about 25 kWh per day. That usually means three or more units, or solar to recharge daily, or load management that sheds the water heater and range.

Solar changes the math because it can refill part of the battery each day. Programs change it too. A battery enrolled in a virtual power plant (VPP) is usually paid for its kW during events, so a bigger inverter and more kWh can raise program pay. A higher backup reserve, meanwhile, keeps energy for outages but leaves less to sell as grid flexibility; see How VPP Programs Pay.

Partial home

Backup panel

Moving critical circuits to a backup panel keeps the load inside one battery’s limits and avoids paying for kWh that only an outage-time dryer would use.

Whole home

Load management

Whole-home backup needs either several units or smart breakers and load controllers that shed big loads automatically when the battery is the only source.

Motors

Check the LRA

Compare a compressor or well pump’s nameplate LRA with the battery’s rating. Soft starters reduce start-up current and can let a smaller system start a large AC unit.

Size it with your own loads

The Battery Size Calculator builds the energy, continuous and peak numbers from a load list and ZIP code. The Backup Runtime Calculator shows hours of backup for a chosen battery.

Method and sources

Load figures are the national planning defaults used in our calculators, each sourced to a manufacturer or sizing guide. Daily kWh = running watts × duty cycle × daily hours in use. Peak = total running watts plus the largest single start-up increment, assuming motors do not start at the same moment.

Battery figures are per unit from manufacturer datasheets; Enphase lists kVA, treated here as kW. The 12.5% sizing reserve follows our Battery Size Calculator. This is a planning estimate, not an electrical design; a licensed installer must confirm loads and code requirements.

Related

Figures are published specifications, prices and program terms checked October 13, 2026. Modeled results are illustrations, not quotes or engineering designs. Program payments are gross, not net profit. Confirm with a licensed installer and the program administrator before buying or enrolling. ← All Guides